Internet Draft UPS MIB August 1993
UPS Management Information Base
August, 1993
Jeffrey D. Case, Ph.D. (Editor)
The University of Tennessee
Department of Computer Science
case@CS.UTK.EDU
1. Abstract
This document is an Internet Draft. Internet Drafts are
working documents of the Internet Engineering Task Force
(IETF), its Areas, and its Working Groups. Note that other
groups may also distribute working documents as Internet
Drafts.
Internet Drafts are valid for a maximum of six months and may
be updated, replaced, or obsoleted by other documents at any
time. It is inappropriate to use Internet Drafts as reference
material or to cite them other than as a "work in progress".
Expires 2/1/94 [Page 1]
Internet Draft UPS MIB August 1993
2. Introduction
This memo defines an experimental portion of the Management
Information Base (MIB) for use with network management
protocols in the Internet community. In particular, it
defines objects for managing uninterruptable power supply
(UPS) systems.
Expires 2/1/94 [Page 2]
Internet Draft UPS MIB August 1993
3. The SNMPv2 Network Management Framework
The SNMPv2 Network Management Framework consists of four major
components. They are:
o RFC 1441 which defines the SMI, the mechanisms used for
describing and naming objects for the purpose of
management.
o RFC 1213 defines MIB-II, the core set of managed objects
for the Internet suite of protocols.
o RFC 1445 which defines the administrative and other
architectural aspects of the framework.
o RFC 1448 which defines the protocol used for network
access to managed objects.
The Framework permits new objects to be defined for the
purpose of experimentation and evaluation.
3.1. Object Definitions
Managed objects are accessed via a virtual information store,
termed the Management Information Base or MIB. Objects in the
MIB are defined using the subset of Abstract Syntax Notation
One (ASN.1) defined in the SMI. In particular, each object
object type is named by an OBJECT IDENTIFIER, an
administratively assigned name. The object type together with
an object instance serves to uniquely identify a specific
instantiation of the object. For human convenience, we often
use a textual string, termed the descriptor, to refer to the
object type.
3.2. Format of Definitions
Section 5 contains the specification of all object types
contained in this MIB module. The object types are defined
using the conventions defined in the SMI, as amended by the
extensions specified in [7,8].
In addition, there are Conformance Groups and Compliance
levels defined per RFC 1444 [9]. They are commented out in
Expires 2/1/94 [Page 3]
Internet Draft UPS MIB August 1993
section 5 so that the MIB may work with SNMP Version 1 MIB
compilers. However, any claim of conformance to a published
version of this document must include a statement indicating
the conformance level. For example, "This product is fully
compliant with the UPS MIB, upsTwoContactCompliance" or "This
product is fully compliant with the UPS MIB,
upsBasicCompliance." It is impossible to be in conformance
with this specification if the claim of conformance fails to
include this required statement.
These statements of compliance take precendence over the
status clauses found in the OBJECT-TYPE definitions which are
included for compatibility with existing SNMP Version 1 MIB
compilers.
4. Overview
This document defines the managed objects for Uninterruptable
Power Supplies which are to be manageable via the Simple
Network Management Protocol (SNMP).
Expires 2/1/94 [Page 4]
Internet Draft UPS MIB August 1993
5. Definitions
UPS-MIB DEFINITIONS ::= BEGIN
IMPORTS
experimental, Counter,
TimeTicks, Gauge FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
InstancePointer, DateAndTime FROM SNMPv2-TC
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
univPowerSupply OBJECT IDENTIFIER ::= { experimental 39 }
-- Note: this should be unintPowerSupply
upsMibDraft2 OBJECT IDENTIFIER ::= { univPowerSupply 12 }
-- Note: univPowerSupply 1-12 were used in earlier drafts.
-- From now on, drafts will use version and subversion numbers
-- under the experimental tree to prevent OID name-space collision
-- when implementing different versions of experimental MIBS.
upsMibE22 OBJECT IDENTIFIER ::= { upsMibDraft2 2 }
-- Experimenal Version 2 minor version 2 (Exp v2.2) of UPS MIB.
--
-- The Device Identification group.
-- All objects in this group are set at device initialization
-- and remain static.
--
upsIdent OBJECT IDENTIFIER ::= { upsMibE22 1 }
upsIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS manufacturer."
::= { upsIdent 1 }
upsIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
ACCESS read-only
STATUS mandatory
Expires 2/1/94 [Page 5]
Internet Draft UPS MIB August 1993
DESCRIPTION
"The UPS Model designation."
::= { upsIdent 2 }
upsIdentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS Firmware software version."
::= { upsIdent 3 }
upsIdentName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"An 8 octet ID string identifying the UPS. This
object should be set by the administrator."
::= { upsIdent 4 }
upsIdentSpecific OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A reference to MIB definitions specific to the
particular UPS being managed. This object may be
used to locate an enterprise-specific MIB for this
device.
If this information is not present, its value
should be set to the OBJECT IDENTIFIER { 0 0 },
which is a syntactically valid object identifier,
and any conformant implementation of ASN.1 and BER
must be able to generate and recognize this
value."
::= { upsIdent 5 }
Expires 2/1/94 [Page 6]
Internet Draft UPS MIB August 1993
--
-- Battery Group
--
upsBattery OBJECT IDENTIFIER ::= { upsMibE22 2 }
upsBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The indication of the capacity remaining in the
UPS system's batteries. A batteryLow value
indicates the UPS will be unable to sustain the
current load, and its services will be lost if
power is not restored."
::= { upsBattery 1 }
upsBatteryTimeOnBattery OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"If the unit is on battery power, the elapsed time
since the UPS has switched to battery power, or
since the network management subsystem rebooted,
whichever is less. Zero shall be returned if the
unit is not on battery power. (Unit of measure:
Seconds)"
::= { upsBattery 2 }
upsBatTimeRemaining OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The estimated time to battery charge depletion.
(Unit of measure: Seconds)"
::= { upsBattery 3 }
upsBatteryVoltage OBJECT-TYPE
Expires 2/1/94 [Page 7]
Internet Draft UPS MIB August 1993
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current battery voltage expressed in 1/10 of
one VDC."
::= { upsBattery 4 }
upsBatTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature of the UPS Battery casing (Unit
of measure: degrees Centigrade)"
::= { upsBattery 5 }
Expires 2/1/94 [Page 8]
Internet Draft UPS MIB August 1993
--
-- Input Group
--
upsInput OBJECT IDENTIFIER ::= { upsMibE22 3 }
upsInputFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current input frequency. (Unit of measure:
1/10 Hertz)"
::= { upsInput 1 }
upsInputLineBads OBJECT-TYPE
SYNTAX Counter
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of input out of tolerance conditions
since the agent started."
::= { upsInput 2 }
upsInputNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of input lines utilized in this
device. This entry indicates the number of rows in
the input table."
::= { upsInput 3 }
upsInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsInputEntry
ACCESS not-accessible
STATUS mandatory
::= { upsInput 4 }
upsInputEntry OBJECT-TYPE
SYNTAX UpsInputEntry
ACCESS not-accessible
STATUS mandatory
Expires 2/1/94 [Page 9]
Internet Draft UPS MIB August 1993
INDEX { upsInputLineIndex }
::= { upsInputTable 1 }
UpsInputEntry ::= SEQUENCE {
upsInputLineIndex INTEGER,
upsInputVoltage INTEGER
}
upsInputLineIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line."
::= { upsInputEntry 1 }
upsInputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input voltage. (Unit of measure: RMS Volt)"
::= { upsInputEntry 2 }
Expires 2/1/94 [Page 10]
Internet Draft UPS MIB August 1993
--
-- The Output group.
--
upsOutput OBJECT IDENTIFIER ::= { upsMibE22 4 }
upsOutputFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current output frequency. (Unit of measure:
1/10 Hertz)"
::= { upsOutput 1 }
upsOutputNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of output lines utilized in this
device. This entry indicates the number of rows in
the output table."
::= { upsOutput 3 }
upsOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsOutputEntry
ACCESS not-accessible
STATUS mandatory
::= { upsOutput 4 }
upsOutputEntry OBJECT-TYPE
SYNTAX UpsOutputEntry
ACCESS not-accessible
STATUS mandatory
INDEX { upsOutputLineIndex }
::= { upsOutputTable 1 }
UpsOutputEntry ::= SEQUENCE {
upsOutputLineIndex INTEGER,
upsOutputVoltage INTEGER,
upsOutputCurrent INTEGER,
upsOutputWatts INTEGER
}
Expires 2/1/94 [Page 11]
Internet Draft UPS MIB August 1993
upsOutputLineIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output line index."
::= { upsOutputEntry 1 }
upsOutputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output voltage. (Unit of measure: RMS Volts)"
::= { upsOutputEntry 2 }
upsOutputCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output current. (Unit of measure: 1/10 Amp)"
::= { upsOutputEntry 3 }
upsOutputWatts OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output power. (Unit of measure: Watt)"
::= { upsOutputEntry 5 }
Expires 2/1/94 [Page 12]
Internet Draft UPS MIB August 1993
--
-- The Bypass group.
--
upsBypass OBJECT IDENTIFIER ::= { upsMibE22 5 }
upsBypassFrequency OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current bypass frequency. (Unit of measure:
1/10 Hertz)"
::= { upsBypass 1 }
upsBypassNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of bypass lines utilized in this
device. This entry indicates the number of rows in
the bypass table."
::= { upsBypass 2 }
upsBypassTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsBypassEntry
ACCESS not-accessible
STATUS mandatory
::= { upsBypass 3 }
upsBypassEntry OBJECT-TYPE
SYNTAX UpsBypassEntry
ACCESS not-accessible
STATUS mandatory
INDEX { upsBypassLineIndex }
::= { upsBypassTable 1 }
UpsBypassEntry ::= SEQUENCE {
upsBypassLineIndex INTEGER,
upsBypassVoltage INTEGER,
upsBypassCurrent INTEGER
}
upsBypassLineIndex OBJECT-TYPE
Expires 2/1/94 [Page 13]
Internet Draft UPS MIB August 1993
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line index."
::= { upsBypassEntry 1 }
upsBypassVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass voltage. (Unit of measure: RMS Volt)"
::= { upsBypassEntry 2 }
upsBypassCurrent OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass current. (Unit of measure: 1/10 Amp)"
::= { upsBypassEntry 3 }
Expires 2/1/94 [Page 14]
Internet Draft UPS MIB August 1993
--
-- The Alarm group.
-- This section needs more attention before we can be done
upsAlarm OBJECT IDENTIFIER ::= { upsMibE22 6 }
upsAlarms OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current number of active alarm conditions."
::= { upsAlarm 1 }
upsAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsAlarmEntry
ACCESS not-accessible
STATUS mandatory
::= { upsAlarm 2 }
upsAlarmEntry OBJECT-TYPE
SYNTAX UpsAlarmEntry
ACCESS not-accessible
STATUS mandatory
INDEX { upsAlarmId }
::= { upsAlarmTable 1 }
UpsAlarmEntry ::= SEQUENCE {
upsAlarmId INTEGER,
upsAlarmDescr OBJECT IDENTIFIER,
upsAlarmTime TimeTicks
}
upsAlarmId OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A unique identifier for an alarm condition. This
value must remain constant."
::= { upsAlarmEntry 1 }
upsAlarmDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
ACCESS read-only
Expires 2/1/94 [Page 15]
Internet Draft UPS MIB August 1993
STATUS mandatory
DESCRIPTION
"A reference to an alarm description object. The
object referenced should not be accessible, but
rather be used to provide a unique description of
the alarm condition."
::= { upsAlarmEntry 2 }
upsAlarmTime OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of sysUpTime when the alarm condition
occurred."
::= { upsAlarmEntry 3 }
--
-- Well Known alarm conditions.
--
upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 }
upsAlarmBatteryBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 1 }
-- Battery needs replacing.
upsAlarmOnBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms 2 }
-- The UPS is drawing power from the battery.
upsAlarmLowBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms 3 }
-- The battery capacity is at a value considered low by
-- the UPS manufacturer
upsAlarmTempBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 4 }
-- A temperature is out of tolerance.
upsAlarmInputBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 5 }
-- An input condition is out of tolerance.
upsAlarmInputFreqError OBJECT IDENTIFIER ::= { upsWellKnownAlarms 6 }
-- The input frequency is out of tolerance.
upsAlarmOutputBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 7 }
-- An output condition is out of tolerance.
upsAlarmOutputOverload OBJECT IDENTIFIER ::= { upsWellKnownAlarms 8 }
Expires 2/1/94 [Page 16]
Internet Draft UPS MIB August 1993
-- The output is loaded over the UPSs capacity.
upsAlarmOnBypass OBJECT IDENTIFIER ::= { upsWellKnownAlarms 9 }
-- The Bypass is currently engaged on the UPS.
upsAlarmBypassBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms 10 }
-- The Bypass is out of tolerance.
upsAlarmStopNoticeIssued OBJECT IDENTIFIER ::= { upsWellKnownAlarms 11 }
-- The UPS had been instructed to shutdown and has
-- performed this shutdown.
upsAlarmChargerFailed OBJECT IDENTIFIER ::= { upsWellKnownAlarms 12 }
-- The UPS charger has failed.
upsAlarmUpsOff OBJECT IDENTIFIER ::= { upsWellKnownAlarms 13 }
-- The UPS is currently in an off state.
upsAlarmInputBrkrOpen OBJECT IDENTIFIER ::= { upsWellKnownAlarms 14 }
-- The input breaker is in an open state.
upsAlarmBypassBrkrOpen OBJECT IDENTIFIER ::= { upsWellKnownAlarms 15 }
-- The bypass breaker is in an open state.
upsAlarmOutputBrkrOpen OBJECT IDENTIFIER ::= { upsWellKnownAlarms 16 }
-- The output breaker is in an open state.
upsAlarmBatteryBrkrOpen OBJECT IDENTIFIER ::= { upsWellKnownAlarms 17 }
-- The battery breaker is in an open state.
upsAlarmSysBypassBrkrOpen OBJECT IDENTIFIER ::= { upsWellKnownAlarms 18 }
-- The system bypass breaker is in an open state.
upsAlarmMaintenanceBypassBreakerClosed OBJECT IDENTIFIER
::= { upsWellKnownAlarms 19 }
-- The maintenance bypass breaker is in a closed state.
upsAlarmFanFailure OBJECT IDENTIFIER ::= { upsWellKnownAlarms 20 }
-- A fan has failed in the UPS.
upsAlarmOnGenerator OBJECT IDENTIFIER ::= { upsWellKnownAlarms 21 }
-- The UPS is drawing power from an auxiliary generator.
Expires 2/1/94 [Page 17]
Internet Draft UPS MIB August 1993
--
-- The Test Group
--
upsTest OBJECT IDENTIFIER ::= { upsMibE22 7 }
upsTestDiagnosticSchedule OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
biweekly(2),
weekly(3),
atTurnOn(4),
never(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The UPS system's automatic battery test
schedule."
::= { upsTest 1 }
upsTestDiagnostics OBJECT-TYPE
SYNTAX INTEGER {
noTest(1),
test(2),
abort(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to test(2) causes the UPS
to perform a diagnostic self test. Setting this
value to noTest(1) has no effect. The value
noTest(1) will always be returned when the
variable is read.
Setting this variable to abort(3) will end a test
in progress."
::= { upsTest 2 }
upsTestDiagnosticsResults OBJECT-TYPE
-- Editor's note: we need to state under what conditions each
-- value is returned.
SYNTAX INTEGER {
passed(1),
Expires 2/1/94 [Page 18]
Internet Draft UPS MIB August 1993
failed(2),
invalidTest(3),
inProgress(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The results of the last UPS diagnostics test
performed."
::= { upsTest 3 }
upsTestLastDiagnosticsDate OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The date the last UPS diagnostics test was
performed."
::= { upsTest 4 }
upsTestIndicators OBJECT-TYPE
SYNTAX INTEGER {
noTest(1),
test(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to test(2) causes the UPS
to perform a front panel indicators (lights) test.
Setting this value to noTest(1) has no effect.
The value noTest(1) will always be returned when
the variable is read."
::= { upsTest 5}
Expires 2/1/94 [Page 19]
Internet Draft UPS MIB August 1993
--
-- The Control group.
--
upsControl OBJECT IDENTIFIER ::= { upsMibE22 8 }
-- Editor's note: the interaction between upsControlOutputOffDelay and
-- upsControlOutputOnDelay is ambiguous and needs to be fixed / clarified.
-- What happens if upsControlOutputOnDelay is less than
-- upsControlOutputOffDelay?
upsControlOutputOffDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this object will stop the output after
the indicated number of seconds. Setting this
object to 0 will cause the UPS to stop the output
immediately. If the output is already off at the
time the delay has counted down, nothing will
happen. Output will remain off until either
external controls or the execution of a
upsControlOutputOnDelay or
upsControlRebootUpsDelay that has run through its
delay turns the power back on."
::= { upsControl 1 }
upsControlOutputOnDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this object will start the output after
the indicated number of seconds. Setting this
object to 0 will cause the UPS to start the output
immediately. If the output is already on at the
time the delay has counted down, nothing will
happen."
::= { upsControl 2 }
upsControlRebootUpsDelay OBJECT-TYPE
SYNTAX INTEGER (0..2147483647)
ACCESS read-write
STATUS mandatory
Expires 2/1/94 [Page 20]
Internet Draft UPS MIB August 1993
DESCRIPTION
"Setting this object will cause the UPS to stop
the output for the indicated after the indicated
number of seconds. The UPS output will remain
stopped for a brief period set by the UPS
manufacturer, after which power will be restored."
::= { upsControl 3 }
Expires 2/1/94 [Page 21]
Internet Draft UPS MIB August 1993
--
-- The Configuration group.
--
upsConfig OBJECT IDENTIFIER ::= { upsMibE22 9 }
upsConfigOutputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The nominal output voltage. (Unit of measure: RMS
volt)"
::= { upsConfig 1 }
upsConfigInputVoltage OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The nominal input voltage. (Unit of measure: RMS
volt)"
::= { upsConfig 2 }
upsConfigOutputVA OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The nominal Volt-Amp rating."
::= { upsConfig 3 }
upsConfigOutputWatts OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The nominal power rating. (Unit of measure:
watt)"
::= { upsConfig 4 }
upsConfigOutputFreq OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
Expires 2/1/94 [Page 22]
Internet Draft UPS MIB August 1993
DESCRIPTION
"The nominal output frequency. (Unit of measure:
1/10 Hertz)"
::= { upsConfig 5 }
upsConfigNominalBatTime OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The nominal battery time. (Unit of measure:
seconds)"
::= { upsConfig 6 }
upsConfigLowBatTime OBJECT-TYPE
SYNTAX INTEGER (0..2147483648)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The available run time once the low battery
condition is reached. (Unit of measure: seconds)"
::= { upsConfig 7 }
upsConfigAutoRestart OBJECT-TYPE
SYNTAX INTEGER { on(1), off(2) }
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this object to 'on' will cause the device
to restart after a shutdown if/when utility power
is present"
::= { upsConfig 8 }
Expires 2/1/94 [Page 23]
Internet Draft UPS MIB August 1993
--
-- The Conformance Groups
--
upsGroups OBJECT IDENTIFIER ::= { upsMibE22 10 }
-- upsCommonGroup OBJECT-GROUP
-- OBJECTS { upsIdentManufacturer, upsIdentModel,
-- upsIdentSoftwareVersion, upsIdentName,
-- upsIdentSpecific }
-- STATUS current
-- DESCRIPTION
-- "The upsCommonGroup define the objects which are common
-- across all managed UPSs."
-- ::= { upsGroups 1 }
-- upsTwoContactGroup OBJECT-GROUP
-- OBJECTS { upsControlOutputOffDelay, upsTestDiagnostics,
-- upsTestDiagnosticsResults }
-- STATUS current
-- DESCRIPTION
-- "The upsTwoContactGroup defines the objects that are
-- common to UPSs that only support the two-contact
-- form of communication."
-- ::= { upsGroups 2 }
upsBasicGroups OBJECT IDENTIFIER ::= { upsGroups 3 }
-- upsBasicBatteryGroup OBJECT-GROUP
-- OBJECTS { upsBatteryStatus, upsBatteryTimeOnBattery,
-- upsBatTimeRemaining, upsBatteryVoltage, upsBatTemperature }
-- STATUS current
-- DESCRIPTION
-- "The upsBasicBatteryGroup defines the objects that are
-- common to the battery groups of basic UPSs."
-- ::= { upsBasicGroups 1 }
-- upsBasicInputGroup OBJECT-GROUP
-- OBJECTS { upsInputFrequency, upsInputLineBads,
-- upsInputNumLines, upsInputLineIndex,
-- upsInputVoltage }
-- STATUS current
-- DESCRIPTION
-- "The upsBasicInputGroup defines the objects that are
-- common to the Input groups of basic UPSs."
Expires 2/1/94 [Page 24]
Internet Draft UPS MIB August 1993
-- ::= { upsBasicGroups 2 }
-- upsBasicOutputGroup OBJECT-GROUP
-- OBJECTS { upsOutputFrequency, upsOutputNumLines,
-- upsOutputLineIndex, upsOutputVoltage,
-- upsOutputCurrent, upsOutputWatts }
-- STATUS current
-- DESCRIPTION
-- "The upsBasicOutputGroup defines the objects that are
-- common to the Output groups of basic UPSs."
-- ::= { upsBasicGroups 3 }
-- upsBasicBypassGroup OBJECT-GROUP
-- OBJECTS { upsBypassFrequency, upsBypassNumLines,
-- upsBypassLineIndex, upsBypassVoltage,
-- upsBypassCurrent }
-- STATUS current
-- DESCRIPTION
-- "The upsBasicBypassGroup defines the objects that are
-- common to the Bypass groups of basic UPSs."
-- ::= { upsBasicGroups 4 }
-- upsBasicAlarmGroup OBJECT-GROUP
-- OBJECTS { upsAlarms, upsAlarmId, upsAlarmDescr,
-- upsAlarmTime }
-- STATUS current
-- DESCRIPTION
-- "The upsBasicAlarmGroup defines the objects that are
-- common to the Alarm groups of basic UPSs."
-- ::= { upsBasicGroups 5 }
-- upsBasicTestGroup OBJECT-GROUP
-- OBJECTS { upsTestDiagnosticSchedule, upsTestDiagnostics,
-- upsTestDiagnosticsResults,
-- upsTestLastDiagnosticsDate, upsTestIndicators }
-- STATUS current
-- DESCRIPTION
-- "The upsBasicTestGroup defines the objects that are
-- common to the Test groups of basic UPSs."
-- ::= { upsBasicGroups 6 }
-- upsBasicControlGroup OBJECT-GROUP
-- OBJECTS { upsControlOutputOffDelay, upsControlOutputOnDelay,
-- upsControlRebootUpsDelay }
-- STATUS current
Expires 2/1/94 [Page 25]
Internet Draft UPS MIB August 1993
-- DESCRIPTION
-- "The upsBasicControlGroup defines the objects that are
-- common to the Control groups of basic UPSs."
-- ::= { upsBasicGroups 7 }
-- upsBasicConfigGroup OBJECT-GROUP
-- OBJECTS { upsConfigOutputVoltage, upsConfigInputVoltage,
-- upsConfigOutputVA, upsConfigOutputWatts,
-- upsConfigOutputFreq, upsConfigNominalBatTime,
-- upsConfigLowBatTime, upsConfigAutoRestart }
-- STATUS current
-- DESCRIPTION
-- "The upsBasicConfigGroup defines the objects that are
-- common to the Config groups of basic UPSs."
-- ::= { upsBasicGroups 8 }
Expires 2/1/94 [Page 26]
Internet Draft UPS MIB August 1993
--
-- Compliance Statements
--
upsCompliances OBJECT IDENTIFIER ::= { upsMibE22 11 }
-- upsTwoContactCompliance MODULE-COMPLIANCE
-- STATUS current
-- DESCRIPTION
-- "The compliance statement for UPSs that only support
-- the old two-contact communication protocol."
-- MODULE
-- MANDATORY-GROUPS { upsCommonGroup, upsTwoContactGroup }
-- ::= { upsCompliances 1 }
-- upsBasicComplaince MODULE-COMPLIANCE
-- STATUS current
-- DESCRIPTION
-- "The compliance statement for UPSs that support
-- basic functions."
-- MODULE
-- MANDATORY-GROUPS { upsCommonGroup, upsBasicBatteryGroup,
-- upsBasicInputGroup, upsBasicOutputGroup,
-- upsBasicAlarmGroup, upsBasicTestGroup,
-- upsBasicControlGroup, upsBasicConfigGroup }
-- GROUP {upsBasicBypassGroup }
-- DESCRIPTION
-- "The upsBasicBypassGroup is only required for
-- UPSs that have a Bypass present."
-- ::= { upsCompliances 2 }
END
Expires 2/1/94 [Page 27]
Internet Draft UPS MIB August 1993
6. Acknowledgements
The UPS MIB represents the combined work of the IETF UPS MIB
Working Group, with particular, substantial authorship
contributions from:
Mike Davison
Fibercom, Inc.
Ray Wasson
Consultant
Roger Draper
Liebert Corporation
Jeff Case
University of Tennessee
Pete Yoest
American Power Conversion
Doug Rademacher
American Power Conversion
Ron Pitt
Network Security Systems, Inc
Terry Zumwalt
International Power Machines
Expires 2/1/94 [Page 28]
Internet Draft UPS MIB August 1993
7. References
[1] M.T. Rose and K. McCloghrie, Structure and Identification
of Management Information for TCP/IP-based internets,
Internet Working Group Request for Comments 1155.
Network Information Center, SRI International, Menlo
Park, California, (May, 1990).
[2] K. McCloghrie and M.T. Rose, Management Information Base
for Network Management of TCP/IP-based internets,
Internet Working Group Request for Comments 1156.
Network Information Center, SRI International, Menlo
Park, California, (May, 1990).
[3] J.D. Case, M.S. Fedor, M.L. Schoffstall, and J.R. Davin,
Simple Network Management Protocol, Internet Working
Group Request for Comments 1157. Network Information
Center, SRI International, Menlo Park, California, (May,
1990).
[4] K. McCloghrie and M.T. Rose (editors), Management
Information Base for Network Management of TCP/IP-based
internets: MIB-II, Internet Working Group Request for
Comments 1213. Network Information Center, SRI
International, Menlo Park, California, (March, 1991).
[5] Information processing systems - Open Systems
Interconnection - Specification of Abstract Syntax
Notation One (ASN.1), International Organization for
Standardization. International Standard 8824, (December,
1987).
[6] Information processing systems - Open Systems
Interconnection - Specification of Basic Encoding Rules
for Abstract Notation One (ASN.1), International
Organization for Standardization. International Standard
8825, (December, 1987).
[7] M.T. Rose, K. McCloghrie (editors), Concise MIB
Definitions, Internet Working Group Request for Comments
1212. Network Information Center, SRI International,
Menlo Park, California, (March, 1991).
[8] M.T. Rose (editor), A Convention for Defining Traps for
use with the SNMP, Internet Working Group Request for
Expires 2/1/94 [Page 29]
Internet Draft UPS MIB August 1993
Comments 1215. Network Information Center, SRI
International, Menlo Park, California, (March, 1991).
[9] J.D. Case, K. McCloghrie, M.T. Rose, and S. Waldbusser,
Conformance Statements for version 2 of the the Simple
Network Management Protocol (SNMPv2), Request for
Comments 1444, SNMP Research, Inc., Hughes LAN Systems,
Dover Beach Consulting, Inc., Carnegie Mellon University,
(April 1993).
Expires 2/1/94 [Page 30]
Internet Draft UPS MIB August 1993
8. Security Considerations
Security issues are not discussed in this memo.
9. Author's Address
Jeffrey D. Case, Ph.D.
The University of Tennessee
Department of Computer Science
107 Ayres Hall
Knoxville, Tennessee 37996
Phone: (615) 573-1434
Email: case@CS.UTK.EDU
Expires 2/1/94 [Page 31]
Internet Draft UPS MIB August 1993
Table of Contents
1 Abstract .............................................. 1
2 Introduction .......................................... 2
3 The SNMPv2 Network Management Framework ............... 3
3.1 Object Definitions .................................. 3
3.2 Format of Definitions ............................... 3
4 Overview .............................................. 4
5 Definitions ........................................... 5
5.1 The Device Identification Group. ................... 5
5.2 The Battery Group ................................... 7
5.3 The Input Group ..................................... 9
5.4 The Output Group .................................... 11
5.5 The Bypass Group .................................... 13
5.6 The Alarm Group ..................................... 15
5.7 The Test Group ...................................... 18
5.8 The Control Group ................................... 20
5.9 The Configuration Group ............................. 22
5.10 The Conformance Groups ............................. 24
5.11 The Compliance Statements .......................... 27
6 Acknowledgements ...................................... 28
7 References ............................................ 29
8 Security Considerations ............................... 31
9 Author's Address ...................................... 31
Expires 2/1/94 [Page 32]